During winter operation, air source heat pump systems often run continuously for heating and domestic hot water production.
Besides common refrigeration faults such as high pressure alarm and low pressure alarm, another frequently reported issue in heat pump projects is:
“The water tank cannot refill automatically.”
When the water level decreases, the system should automatically replenish water through the makeup water system.
However, some users may find:
This problem is usually related to two major areas:
A systematic diagnosis can quickly identify the actual cause.
In a typical air source heat pump system, the water tank is equipped with:
The operating logic is:
Water level decreases
↓
Water level sensor detects low water level
↓
Controller sends refill signal
↓
Solenoid valve opens
↓
Water enters the tank
↓
Water level returns to normal
If any step fails, the tank may not refill.
If opening the manual refill valve does not allow water into the tank, the problem is usually related to the water supply side.
Possible causes:
The incoming water pressure is too low.
Result:
Inspection:
Check:
✔ Building water pressure
✔ Water supply pressure
✔ Water inlet pipeline condition
The makeup water valve may be:
Solution:
Check the valve opening condition and confirm normal water flow.
Some water tanks use mechanical float valves.
If the float:
The water supply will stop even when the water level is low.
Inspection:
Move the float manually and check whether the valve responds correctly.
This situation is more complicated because the water supply system itself may be normal.
Possible causes include:
The water level sensor is responsible for detecting the tank water condition.
Common failures:
Symptoms:
Solution:
Check:
✔ Sensor wiring
✔ Terminal connection
✔ Signal stability
If the sensor position is incorrect:
The controller may receive wrong information.
Examples:
Confirm:
The solenoid valve controls whether water enters the tank.
Common failures:
Causes:
Symptoms:
Solution:
Clean or replace the solenoid valve.
If the coil fails:
Check:
If:
The problem may come from the heat pump control system.
Possible components:
Check whether the controller sends the refill signal.
↓
Check whether the water level relay operates.
↓
Check whether the PCB outputs voltage to the solenoid valve.
If:
Possible causes:
Solution:
Replace relay or main control board if necessary.
In some troubleshooting cases:
The water level sensor is manually lifted out of the water, but automatic refill still does not happen.
Possible reasons:
The controller is not in refill condition.
For example:
Sensor terminal failure
The controller cannot correctly recognize the water level signal.
For installers and service engineers:
Check:
✔ Water pressure
✔ Water inlet valve
✔ Pipeline blockage
↓
Open manual refill valve.
If no water enters:
→ Check water supply system.
↓
Confirm:
↓
Confirm:
↓
Inspect:
To reduce water refill failures:
✔ Ensure sufficient water pressure
✔ Install proper filtration before valves
✔ Check sensor wiring carefully
✔ Test automatic refill function before delivery
✔ Clean water inlet filters regularly
✔ Check solenoid valve operation
✔ Inspect electrical terminals
✔ Verify water level sensor accuracy
A water tank not refilling problem is not always caused by the water supply itself.
The root cause can come from:
The correct troubleshooting sequence is:
Check water supply → Check sensor → Check valve → Check electrical control system
A properly designed and maintained water replenishment system is essential for reliable air source heat pump operation, especially during long winter heating periods.
During winter operation, air source heat pump systems often run continuously for heating and domestic hot water production.
Besides common refrigeration faults such as high pressure alarm and low pressure alarm, another frequently reported issue in heat pump projects is:
“The water tank cannot refill automatically.”
When the water level decreases, the system should automatically replenish water through the makeup water system.
However, some users may find:
This problem is usually related to two major areas:
A systematic diagnosis can quickly identify the actual cause.
In a typical air source heat pump system, the water tank is equipped with:
The operating logic is:
Water level decreases
↓
Water level sensor detects low water level
↓
Controller sends refill signal
↓
Solenoid valve opens
↓
Water enters the tank
↓
Water level returns to normal
If any step fails, the tank may not refill.
If opening the manual refill valve does not allow water into the tank, the problem is usually related to the water supply side.
Possible causes:
The incoming water pressure is too low.
Result:
Inspection:
Check:
✔ Building water pressure
✔ Water supply pressure
✔ Water inlet pipeline condition
The makeup water valve may be:
Solution:
Check the valve opening condition and confirm normal water flow.
Some water tanks use mechanical float valves.
If the float:
The water supply will stop even when the water level is low.
Inspection:
Move the float manually and check whether the valve responds correctly.
This situation is more complicated because the water supply system itself may be normal.
Possible causes include:
The water level sensor is responsible for detecting the tank water condition.
Common failures:
Symptoms:
Solution:
Check:
✔ Sensor wiring
✔ Terminal connection
✔ Signal stability
If the sensor position is incorrect:
The controller may receive wrong information.
Examples:
Confirm:
The solenoid valve controls whether water enters the tank.
Common failures:
Causes:
Symptoms:
Solution:
Clean or replace the solenoid valve.
If the coil fails:
Check:
If:
The problem may come from the heat pump control system.
Possible components:
Check whether the controller sends the refill signal.
↓
Check whether the water level relay operates.
↓
Check whether the PCB outputs voltage to the solenoid valve.
If:
Possible causes:
Solution:
Replace relay or main control board if necessary.
In some troubleshooting cases:
The water level sensor is manually lifted out of the water, but automatic refill still does not happen.
Possible reasons:
The controller is not in refill condition.
For example:
Sensor terminal failure
The controller cannot correctly recognize the water level signal.
For installers and service engineers:
Check:
✔ Water pressure
✔ Water inlet valve
✔ Pipeline blockage
↓
Open manual refill valve.
If no water enters:
→ Check water supply system.
↓
Confirm:
↓
Confirm:
↓
Inspect:
To reduce water refill failures:
✔ Ensure sufficient water pressure
✔ Install proper filtration before valves
✔ Check sensor wiring carefully
✔ Test automatic refill function before delivery
✔ Clean water inlet filters regularly
✔ Check solenoid valve operation
✔ Inspect electrical terminals
✔ Verify water level sensor accuracy
A water tank not refilling problem is not always caused by the water supply itself.
The root cause can come from:
The correct troubleshooting sequence is:
Check water supply → Check sensor → Check valve → Check electrical control system
A properly designed and maintained water replenishment system is essential for reliable air source heat pump operation, especially during long winter heating periods.